General details | | Size of building | 30,000 m2 | Total power | 8,600 kW | Concessionary company | UTE TEM (Tractaments Ecològics del Maresme) | Concession time period | 15 years | Concession start date | 01/01/2010 | | | MBT plant | | Capacity | 190,000 t/year | Operation days | 249 days/year | Operation hours | 15 hours/day on weekdays
| Number of shifts | 2 | Maximum hourly capacity | 30 t/h | Material recovery efficiency (paper, glass, metal, plastic, etc.) | 8,5% input | Recovered organic matter (MOR) | 40% input | Maximum combustible waste | 55% input | | | Waste-to-Energy plant | | Combustible waste PCI estimate | 2,800 kcal/kg | Contract treatment capacity | 140,000 t/year | Number of lines | 2 | Combustion system | Reverse-acting grate
| Unit thermal capacity | 24,000,000 kcal/h | Unit mechanical capacity (PCI 2,800 kcal/kg) | 8.57 t/h | Unit steam generation ratio | 30.2 t/h | Steam pressure | | | Boiler | 67 bar | | Superheater | 62.5 bar | | Turbine | 61 bar | Steam temperature | | | Boiler | 283 ºC | | Superheater | 385 ºC | | Turbine | 380 ºC | | | | Gas treatment system | NOx reduction SNCR (Selective Non Catalytic Reduction) type with urea in combustion chamber | | Semi-dry absorber | | Dry contact reactor | | Active carbon injection | | Fabric filters | | NOx reduction SCR (Selective Catalytic Reduction) type with ammonia | | | Condensation type | Air-cooled condensers | Generation power | 13.55 MW (11.25 MW+2.3 MW) | Energy production | 115,000 MWh/year | Energy self-consumption | 30,000 MWh/year | Electricity sold | 85,000 MWh/year | Energy generation ratio | 820 kWh/t MSW |
|
|  |
|